Toolyard

Tabla de calibres de cable

AWGDiámetro (mm)Diámetro (in)Sección (mm²)Cobre (Ω/km)Cobre (Ω/1000 ft)
4/011.6840.4600107.220.16080.0490
3/010.4050.409685.030.20280.0618
2/09.2660.364867.430.25570.0779
08.2510.324953.480.32240.0983
17.3480.289342.410.40650.1239
26.5440.257633.630.51260.1562
35.8270.229426.670.64640.1970
45.1890.204321.150.81510.2484
54.6210.181916.771.030.3133
64.1150.162013.301.300.3950
73.6650.144310.551.630.4981
83.2640.12858.372.060.6281
92.9060.11446.632.600.7921
102.5880.10195.263.280.9988
112.3050.09074.174.131.26
122.0530.08083.315.211.59
131.8280.07202.626.572.00
141.6280.06412.088.282.53
151.4500.05711.6510.453.18
161.2910.05081.3113.174.02
171.1500.04531.0416.615.06
181.0240.04030.823020.956.38
190.9120.03590.652726.418.05
200.8120.03200.517633.3110.15
210.7230.02850.410542.0012.80
220.6440.02530.325552.9616.14
230.5730.02260.258266.7820.35
240.5110.02010.204784.2125.67
250.4550.01790.1624106.1832.37
260.4050.01590.1288133.9040.81
270.3610.01420.1021168.8451.46
280.3210.01260.0810212.9064.89
290.2860.01130.0642268.4781.83
300.2550.01000.0509338.53103.18
310.2270.00890.0404426.88130.11
320.2020.00800.0320538.28164.07
330.1800.00710.0254678.76206.89
340.1600.00630.0201855.91260.88
350.1430.00560.01601079.28328.96
360.1270.00500.01271360.94414.82
370.1130.00450.01001716.12523.07
380.1010.00400.00802163.98659.58
390.0900.00350.00632728.73831.72
400.0800.00310.00503440.871048.78

Cómo usar Tabla de calibres de cable

  1. Busca el calibre AWG en la primera columna.
  2. Lee su diámetro, su sección en mm² y la resistencia del cable de cobre a 20 °C.

Preguntas frecuentes

¿Cómo paso de AWG a mm²?

Busca el calibre en la tabla: 12 AWG son unos 3,31 mm², 14 AWG unos 2,08 mm² y 10 AWG unos 5,26 mm².

¿Incluye la corriente admisible?

No. La corriente que soporta un cable depende de su aislamiento, de cómo se instala y de la normativa local.

Más calculadoras de ingeniería