Wire Gauge Chart
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Copper (Ω/km) | Copper (Ω/1000 ft) |
| 4/0 | 11.684 | 0.4600 | 107.22 | 0.1608 | 0.0490 |
| 3/0 | 10.405 | 0.4096 | 85.03 | 0.2028 | 0.0618 |
| 2/0 | 9.266 | 0.3648 | 67.43 | 0.2557 | 0.0779 |
| 0 | 8.251 | 0.3249 | 53.48 | 0.3224 | 0.0983 |
| 1 | 7.348 | 0.2893 | 42.41 | 0.4065 | 0.1239 |
| 2 | 6.544 | 0.2576 | 33.63 | 0.5126 | 0.1562 |
| 3 | 5.827 | 0.2294 | 26.67 | 0.6464 | 0.1970 |
| 4 | 5.189 | 0.2043 | 21.15 | 0.8151 | 0.2484 |
| 5 | 4.621 | 0.1819 | 16.77 | 1.03 | 0.3133 |
| 6 | 4.115 | 0.1620 | 13.30 | 1.30 | 0.3950 |
| 7 | 3.665 | 0.1443 | 10.55 | 1.63 | 0.4981 |
| 8 | 3.264 | 0.1285 | 8.37 | 2.06 | 0.6281 |
| 9 | 2.906 | 0.1144 | 6.63 | 2.60 | 0.7921 |
| 10 | 2.588 | 0.1019 | 5.26 | 3.28 | 0.9988 |
| 11 | 2.305 | 0.0907 | 4.17 | 4.13 | 1.26 |
| 12 | 2.053 | 0.0808 | 3.31 | 5.21 | 1.59 |
| 13 | 1.828 | 0.0720 | 2.62 | 6.57 | 2.00 |
| 14 | 1.628 | 0.0641 | 2.08 | 8.28 | 2.53 |
| 15 | 1.450 | 0.0571 | 1.65 | 10.45 | 3.18 |
| 16 | 1.291 | 0.0508 | 1.31 | 13.17 | 4.02 |
| 17 | 1.150 | 0.0453 | 1.04 | 16.61 | 5.06 |
| 18 | 1.024 | 0.0403 | 0.8230 | 20.95 | 6.38 |
| 19 | 0.912 | 0.0359 | 0.6527 | 26.41 | 8.05 |
| 20 | 0.812 | 0.0320 | 0.5176 | 33.31 | 10.15 |
| 21 | 0.723 | 0.0285 | 0.4105 | 42.00 | 12.80 |
| 22 | 0.644 | 0.0253 | 0.3255 | 52.96 | 16.14 |
| 23 | 0.573 | 0.0226 | 0.2582 | 66.78 | 20.35 |
| 24 | 0.511 | 0.0201 | 0.2047 | 84.21 | 25.67 |
| 25 | 0.455 | 0.0179 | 0.1624 | 106.18 | 32.37 |
| 26 | 0.405 | 0.0159 | 0.1288 | 133.90 | 40.81 |
| 27 | 0.361 | 0.0142 | 0.1021 | 168.84 | 51.46 |
| 28 | 0.321 | 0.0126 | 0.0810 | 212.90 | 64.89 |
| 29 | 0.286 | 0.0113 | 0.0642 | 268.47 | 81.83 |
| 30 | 0.255 | 0.0100 | 0.0509 | 338.53 | 103.18 |
| 31 | 0.227 | 0.0089 | 0.0404 | 426.88 | 130.11 |
| 32 | 0.202 | 0.0080 | 0.0320 | 538.28 | 164.07 |
| 33 | 0.180 | 0.0071 | 0.0254 | 678.76 | 206.89 |
| 34 | 0.160 | 0.0063 | 0.0201 | 855.91 | 260.88 |
| 35 | 0.143 | 0.0056 | 0.0160 | 1079.28 | 328.96 |
| 36 | 0.127 | 0.0050 | 0.0127 | 1360.94 | 414.82 |
| 37 | 0.113 | 0.0045 | 0.0100 | 1716.12 | 523.07 |
| 38 | 0.101 | 0.0040 | 0.0080 | 2163.98 | 659.58 |
| 39 | 0.090 | 0.0035 | 0.0063 | 2728.73 | 831.72 |
| 40 | 0.080 | 0.0031 | 0.0050 | 3440.87 | 1048.78 |
How to use Wire Gauge Chart
- Find the AWG size in the first column.
- Read its diameter, cross-section in mm² and the resistance of copper wire at 20 °C.
Frequently asked questions
How do I convert AWG to mm²?
Find the size in the table: 12 AWG is about 3.31 mm², 14 AWG about 2.08 mm² and 10 AWG about 5.26 mm².
Does the chart give current ratings?
No. How much current a wire can carry depends on its insulation, how it is installed and local rules.
More engineering calculators
Ohm's Law CalculatorResistor Color Code CalculatorVoltage Divider CalculatorLED Resistor CalculatorSeries and Parallel CalculatorVoltage Drop CalculatorBattery Life Calculator555 Timer CalculatorTorque CalculatorGear Ratio CalculatorPulley and Belt CalculatorBeam Deflection CalculatorConcrete CalculatorRebar CalculatorBoard Feet CalculatorPaint CalculatorFlooring CalculatorRoof Pitch CalculatorPipe Flow CalculatorReynolds Number CalculatorHeat Loss CalculatorBTU CalculatorSignificant Figures CalculatorScientific Notation ConverterEngineering Notation ConverterTolerance Stack-Up CalculatorScrew Thread ChartSubnet CalculatorNumber Base ConverterDownload Time CalculatorAspect Ratio Calculator